DC cable voltage drop calculator

Low-voltage DC systems lose a lot in thin or long cables. Check the drop and find the cable size that keeps it under your target.

Free, no sign-upFormula shown belowLast reviewed 25 Nov 2026
A
m
Distance from source to load. The calculator counts both the positive and negative wire.
V
More options
%
Many installers aim for 1-3 % on DC circuits. Your local rules may set a limit.

Your results appear here.
Starting values are filled in, so you can press Calculate straight away.

How this calculator works

Current flowing through a cable's resistance loses voltage (Ohm's law). The resistance grows with length and shrinks with cross-section. In a two-wire DC circuit the current travels out and back, so the length counts twice. At 12 V a 1 V drop is over 8 %, while at 48 V the same drop is about 2 %.

Formula

Voltage drop (V) = 2 × length (m) × current (A) × resistivity ÷ cross-section (mm²)
resistivity at 20 °C: copper 0.017241, aluminium 0.0282 Ω·mm²/m
Drop (%) = voltage drop ÷ system voltage × 100

Assumptions and limits

  • Conductor at 20 °C. Warm cables have higher resistance and a larger drop.
  • Voltage drop is one check only: the cable must also be rated for the current, temperature and installation method under your local wiring rules, with correct fuses.

Worked example

15 A over 8 m of 4 mm² at 12 V. 2 × 8 × 15 × 0.017241 ÷ 4 = 1.03 V, which is 8.6 % at 12 V: too much. For 3 % you need at least 11.5 mm², so the next standard size is 16 mm².

Questions

Is this the same for AC?
For single-phase AC with resistive loads it is close. Three-phase and long AC runs need other formulas.

This is an estimate for information only. It is not a quote, a site survey or an electrical design. Ask a qualified installer before you buy or wire anything.